After a power disruption of 20 seconds in a VPLEX environment, the output of the “vault status”
command shows no vaulting processes.
Why did this occur?

A.
The cache vaulting did not exceed the timer period.
B.
It is the expected output, because the command “vault status” doesn’t show information on
cache process at all.
C.
Cache vaulting process has already completed.
D.
Cache vaulting process is still running in background and it is not shown until completed.
Explanation:
Cache vaulting only occurs if the power doesn’t come back up in 30 seconds. The timer period wasn’t exceeded.
Hence the answer is A.
0
0
The pair of SPS units provides DC power to the engines in case there is a loss of AC power. The batteries in the SPSs can hold a charge up to 10 minutes. However, the maximum hold time is 5 minutes