What is the redundant power capacity of the MDS 9509 in this scenario?

A customer has recently deployed a number of Cisco MDS 9509 Multilayer Directors in a new data center. At the time of deployment, it was discovered that 110V AC power circuits had been installed instead of the high-voltage 220V AC circuits that had been ordered. The customer decided to install one of the directors and use the 110V AC circuit. The MDS 9509 is configured with two 2500W AC power supplies. The power supplies are configured in redundant mode.

What is the redundant power capacity of the MDS 9509 in this scenario? 8

What should you do?

Refer to the exhibit.A customer is using an 18/4-Port Multiservice Module in his data center to provide FCIP connectivity to 20 remote sites. The 18/4 MSM has encountered connectivity problems at four of the remote sites. After investigating, the customer’s network administrator found that the 18/4 MSM is sending 2300-byte packets, but the receiving switches at the four remote sites do not support jumbo frames. What should you do? Select the best response.